Acoustical

Acoustical

Acoustical louvers are designed to reduce noise transmission while protecting air intake and exhaust openings. These non-drainable models feature airfoil blades filled with fire- and water-resistant, sound-absorbing insulation to attenuate noise from heavy equipment and mechanical systems. Available in a range of frame depths, blade angles, and spacings, they are constructed from aluminum or steel to meet both acoustic and architectural requirements.

Model Octave Band
Frequency (Hz)
63 125 250 500 1000 2000 4000 8000
LAA-66 Transmission Loss (dB) 166913151414
Free Field Noise Reduction (dB) 712121519212020
LAA-86 Transmission Loss (dB) 145916191613
Free Field Noise Reduction (dB) 710111522252219
LAA-88 Transmission Loss (dB) 156913161311
Free Field Noise Reduction (dB) 711121519221917
LAA-129 Transmission Loss (dB) 28121623282517
Free Field Noise Reduction (dB) 814182229343123
LAA-1212 Transmission Loss (dB) 578131914119
Free Field Noise Reduction (dB) 1513141925201715
LAA-1215 Transmission Loss (dB) 26691211911
Free Field Noise Reduction (dB) 812121518171517
LAA-12AF Transmission Loss (dB) 767131513109
Free Field Noise Reduction (dB) 1412141921191615
Model Octave Band 1 2 3 4 5 6 7 8
Frequency (Hz) 63 125 250 500 1000 2000 4000 8000
LAA-66 Transmission Loss (dB) 166913151414
Free Field Noise Reduction (dB) 712121519212020
LAA-86 Transmission Loss (dB) 145916191613
Free Field Noise Reduction (dB) 710111522252219
LAA-88 Transmission Loss (dB) 156913161311
Free Field Noise Reduction (dB) 711121519221917
LAA-129 Transmission Loss (dB) 28121623282517
Free Field Noise Reduction (dB) 814182229343123
LAA-1212 Transmission Loss (dB) 978131914119
Free Field Noise Reduction (dB) 1513141925201715
Model Description Blade Frame Free Area Water
Penetration
Rating (WPR)
Feet/minute
Pressure
Drop
@ WPR
inches W.C.
Air
Flow
SCFM
Material Thickness
(Frame/Blade/Perf)
Inches
Certification Rating Single Panel Size
Orientation
H - Horiz.
V - Vert.
Angle
Deg.
Spacing
Inches
Depth
Inches
Sq. Ft. % AMCA STC Class Min
W x H
Inches
Max
W x H
Inches
LAA-66 Fixed Non-drainable H 45.0 6.00 6.00 4.23 26 858 0.08 3629 0.080 / 0.061 / 0.032 Y 12 12 x 15 72 x 96
LAA-86 Fixed Non-drainable H 45.0 6.00 8.00 4.24 27 990* 0.10 4198 0.080 / 0.061 / 0.032 - 14 12 x 17 72 x 96
LAA-88 Fixed Non-drainable H 45.0 8.00 8.00 4.01 25 956 0.09 3834 0.080 / 0.061 / 0.032 Y 12 12 x 20 72 x 96
LAA-129 Fixed Non-drainable H 45.0 9.00 12.00 2.38 15 990* 0.10 2356 0.080 / 0.061 / 0.032 - 21 12 x 24 72 x 96
LAA-1212 Fixed Non-drainable H 45.0 12.00 12.00 3.46 22 1089 0.10 3931 0.080 / 0.061 / 0.032 Y 14 12 x 30 72 x 96
LAA-1215 Fixed Non-drainable H 45.0 15.00 12.00 5.53 35 1173* 0.13 6487 0.080 / 0.061 / 0.032 - 10 12 x 36 72 x 96
LAA-12AF Fixed Non-drainable H 45.0 12.00 12.00 3.49 22 1127 0.06 4001 0.080 / 0.061 / 0.032 Y 13 12 x 24 72 x 96
Notes:
AMCA certified performance based on 4' x 4' louver
Standard construction designed for 25 PSF (100 mph) wind load for maximum single panel size
*Pressure drop velocity only